SPECIFICATIONS
Operating Voltage Range: 9~32VDC Volts
Nominal Operating Resistance: 300Ω
Relay Contact Ratings: 2A/30VDC
Operating Humidity Range: 95% RH, Non-condensing
Operating Temperature Range: -10°C to 50°C (14°F to 122°F)
Dimensions: W89mm ,H93mm, D26mm
base Dimensions: W87mm ,H87mm, D31.5mm
Weight: Net Weight 125g (with base)
Colour/Case Material: Red/ ABS
INSTALLATION
This manual should be left with the owner/user of this equipment.
The call points should be installed in a position where they will not be subjected to mechanical stresses , and
where the temperature is within the operating temperature range.
Areas where there are , or are likely to be, aggressive substances should be avoided .
TO ACTIVATE ALARM
The conventional manual call point designed for conventional fire alarm system for reporting fire or emergency
condition by its button latches. The call point has one 300 ohm resistor is used on the PCB board between
Zone+ and Zone- or one relay contact (NO, COM, NC ) output when the button is pressed.